Trade Partner Portal Login

Industrial Door Manufacturers Alliance Doors

Trade Partner Portal Login

Alliance Door Engineering Industrial Doors Logo

S35 - The Arctic Hare Insulated High Speed Roller Shutter

TECHNICAL SPECIFICATION

Operation – Keyswitch / Rockerswitch

Typical Application
Kitchen Servery / Reception Counter

MAXIMUM SIZE
3000mm WIDE x 3000mm HIGH

CURTAIN
2” flat lath galvanised to BS729:1971, 20swg (0.9mm) thick. Alternate laths are fitted with high quality pressed steel endlocks, which are double pop riveted to prevent lateral movement. The curtain is attached to the shutter barrel using high tensile hexagon head set screws. A high strength inverted “T” section bottom rail is added to the base of the curtain for rigidity and fire integrity.

BARREL
4” Outside diameter electric resistance welded tube (BS6323) which supports the steel bearing blocks. 240 volt tubular motor, complete with manual overide, limits and planetary gearbox.

FLAGS
Endplates are constructed from flat 6mm thick mild steel plate (BS 1449) bolted to the endplate using high tensile hexagon head bolts. The motor drive endplate is fitted with a motor mounting plate using hexagon head high tensile set screws, the non-motor end is fitted with a lost bobbin arrangement. Fixing angles are formed using hot rolled angle section, 75mm x 50mm x 6mm, attached to the fixing angles are the galvanised (BS 729:1971) shutter guides, the guide section is typically 2 1/2” in depth x 1” inside dimension, the guide thickness is 3mm. The flags are coated in a black primer paint finish.

HOOD
Slotted Fire Hood made from 20swg mild steel, galvanised to BS729:1971, c/w 50mm x 9mm obround shaped slots.

SAFETY
Safety brake required if the shutter is fitted covering a pedestrian access/egress points. Please refer to your own risk assessment.

ELECTRICAL REQUIREMENTS

SINGLE PHASE
13 AMP FUSED SPUR / ISOLATOR

SUPPLY REQUIRED WITHIN 1 METRE OF MOTOR SIDE

POWER / ACTIVATION DETAILS

PHOENIX FIRE SHUTTERS ARE LINKED INTO THE FIRE ALARM SYSTEM AS STANDARD, OTHERWISE A LOCAL SMOKE DETECTOR WILL BE REQUIRED (BY OTHERS) TO ACTIVATE THE SHUTTER. THE FIRE SIGNAL REQUIRED IS A NORMALLY OPEN VOLT FREE SIGNAL.

A PHOENIX FIRE SHUTTER MUST HAVE A “MAINTAINED SUPPLY”, A BATTERY BACK UP SYSTEM CAN BE PROVIDED AT AN EXTRA COST.

RELEASE MECHANISM

ACTIVATED UPON RECEIPT OF SIGNAL FROM FIRE ALARM / SMOKE DETECTOR. THE TUBULAR MOTOR DRIVES THE SHUTTER TO THE FULLY CLOSED POSITION.
OPTION – FIRE DOOR INTERFACE PANELS & REPEATERS

ACTIVATED UPON RECEIPT OF SIGNAL FROM FIRE ALARM / SMOKE DETECTOR. A TIME DELAY CAN BE PROGRAMMED IN TO THE F.D.I. PANEL, WHEREBY THE SIGNAL WILL BE HELD FROM THE SHUTTER UNTIL THE PROGRAMMED TIME HAS ELAPSED. DURING THE TIME DELAY THE F.D.I. PANEL WILL FLASH “FIRE DOOR CLOSING”, SIMULTANEOULSY AN AUDIBLE ALARM WILL SOUND. ONCE THE TIME HAS ELAPSED, THE DOOR WILL DRIVE DOWN UNDER POWER UNTIL IT HITS THE BOTTOM LIMIT.

 

WEIGHT
35 KGs Per Square Metre

Space Requirements

Face Fix

Maximum Width: 2500
Motor Sideroom: 150mm
Non-Motor Sideroom: 76mm Per Side
With Brake: 150mm, 150mm Per Side

Between Fix

Maximum Width: 2500
Motor Sideroom: Lose 178mm
Non-Motor Sideroom: Lose 70mm
With Brake: Lose 178mm, Lose 178mm

Maximum Height: 2600, 3000